The AEMC Instruments 8345, part of the PowerPad® IV series, is a highly advanced and portable Class A Power Quality Analyzer. It’s designed for electrical professionals to comprehensively diagnose, measure, and analyze power quality and energy consumption in single-phase, two-phase, and three-phase electrical networks.
Features:
Capabilities:
Specifications:
Applications:
Resources:
Features:
- Multi-Input Channels: Features 5 voltage inputs (up to 1000 VAC/DC) and 4 current inputs, all isolated, allowing for comprehensive monitoring of multi-phase systems.
- High Sampling Rates: Provides high sampling rates (Voltage 400 kSps, Current 200 kSps, Surge 2 MSps) to capture detailed waveform information.
- Wide Measurement Range:
- Voltage: 5 V to 1000 VAC and VDC.
- Current: TRMS current measurement (sensor dependent, e.g., up to 3000 A or 12000 A with appropriate flexible current sensors).
- Frequency: 42.50 Hz to 69.00 Hz.
- Intuitive User Interface: Large 7-inch color LCD touchscreen display (800 x 480 WVGA) for easy setup, real-time waveform viewing, and data analysis.
- Extensive Data Logging & Storage:
- Records over 900 parameters.
- Trend recording with programmable sampling periods (e.g., 200 ms for 3 days, 1s for 15 days, 3s for 45 days).
- 16 GB SD card for data storage (snapshots, transients, alarms, trends).
- No maximum for transient and inrush capture (limited by SD card space).
Capabilities:
- Advanced Power Quality Diagnostics:
- Harmonics & Interharmonics: Measures and displays harmonics up to the 127th order and interharmonics up to the 126th order (IEC 61000-4-7 compliant) for in-depth analysis of waveform distortion.
- Flicker: Calculates and measures Pst (short-term) and Plt (long-term) flicker (IEC 61000-4-15 compliant).
- Transients & Shockwaves: Captures fast transient events and shockwaves (up to 12 kV sampled every 500 ns), which are critical for identifying voltage spikes from lightning or switching operations.
- True InRush®: Records RMS and peak inrush currents over extended periods (up to 30 minutes) to analyze motor startup and load behavior.
- Voltage Unbalance: Calculates voltage unbalance for assessing phase loading and system health.
- Power Factor (PF), Displacement Power Factor (DPF), Crest Factor (CF), Total Harmonic Distortion (THD).
- K Factor & FHL calculations.
- Carrier Current Detection.
Specifications:
ELECTRICAL | ||||||
---|---|---|---|---|---|---|
Measurement Frequency | Measurement Range without Ratio (with unity ratio) | |||||
Min | Max | |||||
42.50 Hz | 69.00 Hz | |||||
Inputs | 5 Voltage / 4 Current, isolated | |||||
Voltage | 5 V to 1,000 VAC and VDC | |||||
Harmonics Mode | DC to 127th order; < 3% Udin | |||||
Interharmonics Mode | 0 to 126th order; < 0.5% Udin | |||||
Inrush & Transient Capture (number) | No maximum (limited by SD card) | |||||
Shockwaves (Fast transient) | Up to 12 kV sampled every 500 ns | |||||
Flicker (Pst) | < 0,1 | |||||
Voltage Unbalance (u0,u2) | 0.5 to 5 % (absolute); ±0.15 % (absolute) | |||||
Trend Recording recommended) | > 900 parameters 3 days with a sampling period of 200 ms 15 days with a sampling period of 1 s 45 days with a sampling period of 3 s | |||||
Sampling Rate | Voltage 400 kSps / Current 200 kSps / Surge 2 MSps | |||||
Alarm Mode Types / Number | 52 / 20,000 with Email notifications | |||||
Real-time Mode | Yes | |||||
Power Mode | Yes | |||||
Energy Mode | Composite | |||||
Unbalance Mode | Yes | |||||
Screenshots | No maximum (limited by SD card) | |||||
Power Supply | Power from phase from 100 to 1000 V AC/DC with external supply block (included) | |||||
Carrier Current Detection | Yes | |||||
Battery | 5.8 A•h Li-ion battery pack (included) ≤6 hrs w/ display on; ≤10 hrs w/ display off | |||||
MECHANICAL | ||||||
Data Storage | 16 GB SD-Card (included) for snapshot,transients, alarms and trend recording | |||||
Display | 7 in color LCD touch screen: 800 x 480 (WVGA) | |||||
Clock / GPS | Yes, built-in | |||||
Operating Temperature | 32 °F to 104 °F [+0 °C; +40 °C] | |||||
Communication | USB, Ethernet, Wi-Fi, Web server, DataViewSyncâ„¢, USB port (type A) | |||||
Dimensions | (7.87 x 11.22 x 2.17) in (200 x 285 x 55) mm | |||||
Weight (meter only) | 4.19 lbs (1.9 kg) | |||||
COMPLIANCE & STANDARDS | ||||||
Safety | IEC 61010 1000 V CAT IV![]() | |||||
Ingress Protection | IP54 | |||||
Environmental | IEC 61557-12 & IEC 62586 | |||||
Measurement Standard | IEC 61000-4-30 (Ed 3) Class A (Full) | |||||
EN50160 Monitoring Mode | Yes, with DataView® software | |||||
Warranty | *3 years (registration must be done within 30 days of the date of purchase) |
Applications:
- Electrical Maintenance: Troubleshooting power quality issues, identifying the root cause of equipment malfunctions, and performing preventative maintenance.
- Energy Audits & Efficiency Studies: Analyzing energy consumption, identifying areas for efficiency improvement, and validating energy-saving initiatives.
- Load Balancing & Load Start-up Measurements: Characterizing loads, assessing motor start-up impacts, and ensuring proper load distribution.
- Harmonic Analysis: Diagnosing problems caused by harmonic distortion (e.g., overheating transformers, neutral conductor issues).
- Flicker Monitoring: Assessing voltage fluctuations that can cause noticeable light flicker.
- Capacitor Bank Sizing & Power Factor Correction.
- Transformer Analysis (Derating).
- Failure of Switchgear or its Components.
- Tripping of Circuit Breakers and Differentials.
- Inspecting and maintaining industrial and commercial electrical installations.
- Measurements on photovoltaic installations.
Resources: