The AEMC Chauvin Arnoux C.A 6116NÂ is a durable and reliable instrument that is built to withstand the rigors of daily use. It features a large, backlit display that makes it easy to read measurements in all lighting conditions. The instrument also includes a variety of safety features, such as a built-in overvoltage protection and a current limiting circuit.
The AEMC C.A 6116N is a multi-function installation tester that is used to test electrical installations for compliance with national and international standards. It is a versatile instrument that can be used for a variety of tasks, including:
Tasks:
Key Features:
Specifications:
Resources:
Tasks:
- Continuity testing
- Resistance testing
- Insulation testing
- Earth and selective earth testing
- Loop impedance testing
- Type A and AC RCD testing
- Voltage, frequency, current, active power, harmonics, and phase rotation testing
Key Features:
Here are some of the key features of the AEMC Chauvin Arnoux C.A 6116N:
- Multi-function instrument for testing a variety of electrical parameters
- Durable and reliable construction
- Large, backlit display
- Variety of safety features
Specifications:
| CONTINUITY / RESISTANCE | |
| I Rated  • Range  • Resolution | I > 200 mA  • 39.99 Ω  • 0.01Ω  ± (1.5 % of R + 2 cts) 12 mA  • (39.99 and 399.9) Ω  • (0.01 and 0.1) Ω  •± (1.5 % of R + 5 cts) with beep |
| Range • Resolution • Accuracy | 4 kΩ • 1 Ω  • ±(1.5 % of R + 5 cts) (40 to 400) kΩ  •  (10 – 100) Ω  • ±(1.5 % of R + 2 cts) |
| INSULATIONÂ Â Â Â Â Â Â Â Â | |
| Rated Voltage | U test: (50, 100, 250, 500, and 1000) VDC |
| Range • Resolution • Accuracy | 0.01 MΩ to 2 GΩ   •  0 kΩ to 1 MΩ  • ± (5 % of R + 3 cts) |
| Short Circuit Current | ≤ 3 mA |
| 3P GROUND | |
| Range •  Resolution •  Accuracy | (0.50 to 40) Ω  • 0.01 Ω  • ± (2 % of R + 10 cts) (40 Ω to 15 kΩ)  • (0.1 to 1) Ω • ± (2 % of R + 2 cts ) (15 to 40) kΩ  • 10 Ω  • ± (10 % of R + 2 cts ) |
| Others | Measurement of resistance of auxiliary stakes RH & RS (up to 40 kΩ) |
| Ufk | Complies with SEV 3569 |
| 1P SELECTIVE GROUND | |
| Range Resolution Accuracy | (0.20 to 39.99) Ω (40 to 399.9) Ω (0.01 – 0.1) Ω ± (10 % of R + 10 cts) (ISel via clamp) |
| LOOP IMPEDANCE (Zs (L-PE0 AND Zi (L-N OR L-L) – 1P LIVE GROUND | |
| Live Ground Installation Voltage Frequecy | (90 to 500) V (15.8 to 17.5) Hz (45 to 65) Hz |
| High-current mode with TRIP Zs (L- PE) & Zi (L- N or L – L) Range • Resolution • Accuracy | Max. test current: 7.5 A  (0.100 to 0.5) Ω • 0.001 Ω • ± (10 % of R + 20 cts) (0.5 to 3.999) Ω • 0.001 Ω • ± (5 % of R + 20 cts) (3.999 to 39.99) Ω • 0.01 Ω • ±(5 % of R + 2 cts) (39.99 to 399.99) Ω • 0.1 Ω • ± (5 % of R + 2 cts) |
| NO TRIP mode (Zs (L – PE) Only) Range •  Resolution •  Accuracy | Test current (6, 9,and 12) mA (as required) (0.20 to 0.99) Ω • 0.01 Ω • ± (15 % of R + 10 cts) (1.00 to 1.99) Ω • 0.01 Ω • ± (15 % of R + 3 cts) (2.00 to 39.99) Ω • 0.01 Ω • ± (10 % of R + 3 cts) (40.00 to 399.9) Ω • 0.1Ω • ± (5 % of R + 2 cts) (400 to 3999) Ω • 1 Ω • ± (5 % of R + 2c ts) |
| Calculation of IK short circuit current (PFC (Zs), I Sc PSCC (Zi) | Fault current and short-circuit current: (0.1 to 20) kA |
| Others | Measurement of the resistive and inductive components of Zs and Zi impedances |
| AC and type RCDs | |
| Installation Voltage Frequency | (90 to 500 ) VÂ (15.8 to 17.5) Hz and (45 to 65) Hz |
| IΔn | 10/30/100/500/650/1000 (90 to 280) V or variable ramp and pulse test |
| N-Trip Test | At ½ IΔn – Duration 1000 ms or 2000 ms |
| Ramp Mode | 0.2 to 0.5 x IΔn(Uf) / 0.3 x IΔn to 1.06 IΔn increments of 3.3% x IΔn |
| Trip test: R: Range / Resolution / Accuracy | 0.2 to 0.5 x IΔn(Uf) / 0.5 x IΔn / 2 x IΔn(selective) / 5 x IΔn Pulse: 0 to 500ms/0.1 and 1ms / 2ms, Ramp mode: 0 to 200ms / 0.1ms / 2 ms |
| OTHER MEASUREMENTS | |
| Current by Current Probe C177A | 5.0 mA t0 199.9 A |
| Current by Current Probe MN77 | (1 mA*) 5.0 mA to 19.99 A |
| Voltage | 0 to 550 VAC/DC / DC and (158 to 500) Hz |
| Frequency | (10 to 500) Hz |
| Phase Rotation | (20 to 500) VAC |
| Active Power | (0 to 110) kW single phase – (0 to 330) kW three-phase Simultaneous display of voltage and current waveforms |
| Harmonics | Voltage and Current up to 50th order THD-F / THD-R |
| Â SPECIFICATIONS | |
| Display | Large 5.7 inch backlit graphic color LCD 320 x 240 pixels |
| Storage/Communication | USB for data transfer to DataView® software (included) |
| Power Supply | Rechargeable Lithium-Ion 10.8 V, 5.8 A • h |
| Battery Life | Up to 30 hours |
| Protection | IP 53 / IK04 |
| Dimensions Weight | (11 x 7.48 x 5.04) in (280 x 190 x 128) mm 4.85 lbs (2.2 kg) |
| EMC | IEC61326-1 |
| Electrical Safety | IEC61010-1 – 600 V CAT III 300 V CAT IV – IEC 61557 |
Resources:









